in EN 779 filter classes F7, F8 and F9 and ISO 16890 filter classes ISO ePM1, ISO ePM2,5, ISO ePM10
Compact filters owe their name to their compact, space-saving construction. They provide maximum media area within minimum volume, offering an optimum combination of high filtration efficiency and low pressure drop. As a result, compact filters attain long service life even when used with high volume flow rates and high inlet particulate concentrations.
EMW® has a proven track record spanning more than 30 years as a manufacturer and supplier of minipleat compact filters for gas turbine inlet air filtration. Whatever your gas turbine, its operating mode site air conditions and maintenance intervals, we can provide the best air filter for the job at hand.
Our GT compact filters offer up to 38 m² media area in a single space-saving filter unit. A cast airtight seam joins the water-repellent media to the aerodynamically optimized plastic frame. A fully synthetic nonwoven fabric mat on the outlet side enhances pleat strength, ensuring secure operation even with pressure drops in excess of 5000 Pa and under other heavy-duty conditions.
Can be stopped and rotated!
For efficient particulate removal even under heavy-duty operating conditions.
Innovative minipleat technology provides maximum filter media area in the smallest of spaces.
EMW® minipleat compact filters for gas turbine applications are equipped with a pleat reinforcing mat on their outlet side. This reinforcement system provides superb toughness and other advantages over conventional metal or plastic reinforcing grids. The result: heavy-duty strength and outstanding dependability even under extreme conditions such as pressure drops greater than 5000 Pa.
EMW® GT compact filters incorporate a specially designed plastic frame which minimizes turbulent air flow in gas turbine inlet air filtration. GT compact filters provide further benefits as well: they are easy to install and fully incinerable for simple disposal after use.
The filter media is joined to the frame by an airtight full-perimeter joint. The joined module is finished with a continuous foamed-in-place seal applied on the inlet or outlet side as desired.
Filter type | MPK 47-20 GT | MPK 37-23 GT | MPK 47-31 GT |
---|---|---|---|
Filter class according to EN 779 | F7 | F7 | F7 |
Dimensions | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm |
Average Efficiency of 0.4 µm particles | ≥ 80 | ≥ 80 | ≥ 80 |
Nominal air flow rate [m³/h] | 3400 (4250) | 3400 (4250) | 3400 (4250) |
Initial pressure drop | 95 / 135 | 55 / 80 | 75 / 110 |
Filter type | MPK 48-20 GT | MPK 38-23 GT | MPK 48-31 GT |
---|---|---|---|
Filter class according to EN 779 | F8 | F8 | F8 |
Dimensions | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm |
Average Efficiency of 0.4 µm particles | ≥ 90 | ≥ 90 | ≥ 90 |
Nominal air flow rate [m³/h] | 3400 (4250) | 3400 (4250) | 3400 (4250) |
Initial pressure drop | 100 / 150 | 85 / 120 | 80 / 120 |
Filter type | MPK 49-20 GT | MPK 39-23 GT | MPK 49-31 GT |
---|---|---|---|
Filter class according to EN 779 | F9 | F9 | F9 |
Dimensions | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm |
Average Efficiency of 0.4 µm particles | ≥ 95 | ≥ 95 | ≥ 95 |
Nominal air flow rate [m³/h] | 3400 (4250) | 3400 (4250) | 3400 (4250) |
Initial pressure drop | 120 / 170 | 85 / 120 | 94 / 120 |
Filter type | MPK 47-20 GT | MPK 37-23 GT | MPK 47-31 GT | MPK 48-20 GT | MPK 38-23 GT | MPK 48-31 GT | MPK 49-20 GT | MPK 39-23 GT | MPK 49-31 GT |
---|---|---|---|---|---|---|---|---|---|
Dimensions | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm | 592 x 592 x 296 mm | 592 x 592 x 400 mm | 592 x 592 x 400 mm |
Designated Filter Group ISO 16890 | ISO ePM1 60% | ISO ePM 1 55% | ISO ePM 1 55% | ISO ePM 1 65% | ISO ePM 1 65% | ISO ePM 1 70% | ISO ePM 1 80% | ISO ePM 1 85% | ISO ePM 1 80% |
Further Filter Groups ISO 16890 | PM2,5 70% | PM10 90% | PM2,5 65% | PM10 85% | PM2,5 65% | PM10 85% | PM2,5 75% | PM10 90% | PM2,5 75% | PM10 90% | PM2,5 75% | PM10 90% | PM2,5 85% | PM10 95% | PM2,5 85% | PM10 95% | PM2,5 85% | PM10 95% |
Nominal air flow rate [m³/h] | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) | 3400 (4250) |
Initial pressure drop | 95 / 135 | 55 / 80 | 75 / 110 | 100 / 150 | 85 / 120 | 80 / 120 | 120 / 170 | 85 / 120 | 94 / 120 |
Filter type | MPK 46-20 GT | MPK 36-23 GT |
---|---|---|
Dimensions | 592 x 592 x 296 mm | 592 x 592 x 400 mm |
Designated Filter Group ISO 16890 | ISO ePM 10 75% | ISO ePM 10 75% |
Nominal air flow rate [m³/h] | 3400 (4250) | 3400 (4250) |
Initial pressure drop | 80 / 125 | 50 / 70 |
All data given are based on test results determined according to EN 779 or ISO 16890. The data are average values subject to tolerances due to normal production fluctuations. The figures are only suitable for comparison with those of other products tested according to the same standard. Dust holding capacity according EN 779 is measured till a final pressure drop of 450 Pa, whereas according ISO 16890 the dust holding capacity is measured till 300 Pa. If higher final pressure drop levels are suitable, the dust holding capacity will be accordingly higher.